dc.contributor.authorRodríguez Hidalgo, M. C.-
dc.contributor.authorRodríguez Aumente, P.-
dc.contributor.authorIzquierdo, M.-
dc.contributor.authorLecuona Neumann, Antonio-
dc.contributor.authorSalgado Manguala, R.-
dc.date.accessioned2010-01-08T12:14:22Z-
dc.date.available2010-01-08T12:14:22Z-
dc.date.issued2008-10-
dc.identifier.citationApplied Thermal Engineering 28(14-15): 1734-1744 (2008)en_US
dc.identifier.issn1359-4311-
dc.identifier.urihttp://hdl.handle.net/10261/19911-
dc.description.abstractAir conditioning (AC) is spreading in Spain, where summer weather reaches temperatures above 35 °C. This causes the increase, not only of electricity consumption, but also organic refrigerant leakage due to the use of vapour-compression machines. An experimental research on solar absorption cooling has been carried out at Universidad Carlos III de Madrid (UC3M) in order to evaluate alternative lower impact AC techniques. The facility is based on an on-Campus field of 50 m2 flat plate solar collectors driving a single-effect commercial LiBr/H2O absorption machine through a hot-water storage tank. Experimental operating parameters have been recorded during 2004 summer season in periods of 10 min showing all the relevant figures of merit. Results show that absorption machine cooling power reaches 6–10 kW, with a generator driving power input of 10–15 kW, achieving a mean cooling period of 6.5 h of complete solar autonomy on a seasonal average day. In order to measure the market applicability of this setup, the instantaneous thermal load and demand of a single detached housing of total floorspace of 90 m2 were calculated using standard techniques. Its peak ranged from 6 to 8 kW. Seasonal solar fraction of AC provided by the facility reached 56%. This work shows results on system performance, economic investing, energy and economic savings and includes environmental impact reduction, when comparing the solar absorption system with a conventional vapour-compression machine. A sensitivity study to solar field size has been performed to yield the reasonable share of the absorption machine in the seasonal cooling demand. The result indicates that the dimensioning of the facility is correct.en_US
dc.description.sponsorshipThis work has been partially funded by the Spanish government research grant M. C. y T. CLIMABCAR project DPI 2003-01567, ENE 2005-08255-CO2-01 and MINICOM project (FIT 0204-2004-68 and FIT 020100-2003-233), Project UC3M-IME-05-011 by the Local Government of Madrid. Their contribution is greatly appreciated.en_US
dc.format.extent98816 bytes-
dc.format.mimetypeapplication/vnd.ms-excel-
dc.language.isoengen_US
dc.publisherElsevieren_US
dc.rightsclosedAccessen_US
dc.subjectSolar energyen_US
dc.subjectAbsorption coolingen_US
dc.subjectEnvironmental impact reductionen_US
dc.subjectSolar air conditioningen_US
dc.subjectEnergy savingen_US
dc.subjectSustainabilityen_US
dc.titleEnergy and carbon emission savings in Spanish housing air-conditioning using solar driven absorption systemen_US
dc.typeartículoen_US
dc.identifier.doi10.1016/j.applthermaleng.2007.11.013-
dc.description.peerreviewedPeer revieweden_US
dc.relation.publisherversionhttp://dx.doi.org/10.1016/j.applthermaleng.2007.11.013en_US
dc.type.coarhttp://purl.org/coar/resource_type/c_6501es_ES
item.openairetypeartículo-
item.grantfulltextnone-
item.cerifentitytypePublications-
item.openairecristypehttp://purl.org/coar/resource_type/c_18cf-
item.fulltextNo Fulltext-
item.languageiso639-1en-
Aparece en las colecciones: (IETCC) Artículos
Show simple item record

CORE Recommender

SCOPUSTM   
Citations

78
checked on 11-abr-2024

WEB OF SCIENCETM
Citations

69
checked on 14-feb-2024

Page view(s)

365
checked on 18-abr-2024

Google ScholarTM

Check

Altmetric

Altmetric


NOTA: Los ítems de Digital.CSIC están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.